PV INPUT
Max. PV input voltageâ : 1100 V
Nominal PV input voltage: 580 V / 600 V
Operating voltage range:Â 200 ~ 1000 V
MPPT voltage rangeâĄ: 180 ~ 1000 V
Start-up voltage: 200 V
No. of MPP trackers / Strings per MPP tracker: 9 / 2 | 12 / 2âĢ
Max. input current per MPPT(MPPT1/2): 32 A
Max. input short circuit current per MPPT(MPPT1/2): 46 A
AC OUTPUT
Rated output power: 125 kW
Rated output current: 189.4 A/ 181.2 A
Max. output apparent power: 132 kVA
Max. output continuous current: 200 A / 191.3 A
Nominal AC voltage: 3 / (N) / PE, 220 / 380 V | 3 / (N) / PE, 230 / 400 V
Nominal AC frequency: 50 Hz / 60 Hz
AC frequency rangeâĢ: 50 Âą 5 Hz / 60 Âą 5 Hz
Adjustable Power Factor range: ~ 1 (0.8 lagging to 0.8 leading)
THDi (rated power): < 3%
Efficiency
Max. Efficiency: 98.6%
European Efficiency: 98.3%
ENVIRONMENT LIMIT
Ingress protection: IP66
Operating ambient temperature range: -25 ~ 60°C
Max. operating altitude: 4000 m
Relative humidity: 0 ~ 100% RH (condensing)
Overvoltage Category: Mains: III / PV: II
Protection
DC injection monitoring, Back feed current monitoring, Residual current detection, Over temperature
protection, AC overcurrent protection, AC short-circuit protection.
Active anti-islanding method: Frequency shift
Surge protection (DC / AC): Type II / Type II(Optional)
Arc-fault circuit interrupter (AFCI): Optional
Anti-PID: External
General Data
Net weight: 83 kg
Cooling concept: Smart cooling
Communication interfaces:Â RS485/DRM
Power consumption (night): < 10 W
Topology: Non-isolated
Certificates and approvals: VDE4105, EN 50549, AS 4777.2, VDE4105, G98/G99, IEC 61727, IEC 62116, IEC 61683,
IEC 60068, EN 50530, NB/T 32004, IEC/EN 62109-1, IEC/EN 62109-2
AC auxiliary power supply (APS): Build-in
Reviews